Fire Alarm Sounder Levels in Healthcare: I.S. 3218:2024 Compliance | Phoenix STS

Critical Question

Are fire alarm sound levels designed for life safety actually creating new risks in healthcare environments where residents cannot independently evacuate? Evidence from real-world incidents suggests that high sound levels can impede evacuation effectiveness.

Fire alarm systems are designed to protect lives by providing early warning of fire, giving occupants time to evacuate or be assisted. In healthcare environments such as nursing homes and hospitals, the balance between safety and resident welfare is delicate, given that many occupants may be immobile, have cognitive impairments, or be particularly sensitive to sound.

I.S. 3218:2024 sets stringent fire detection and alarm system requirements, including sound levels which must meet a minimum of 75 dB(A) in sleeping areas. While these levels ensure audibility and compliance with the standard, they also present a significant risk in healthcare settings where independent evacuation is often not feasible.

This article examines the standard’s requirements, the risks they introduce in healthcare settings, real-world evidence of these risks, and practical mitigation strategies.

I.S. 3218:2024 Requirements: Sound Level Specifications

What the Standard Requires

I.S. 3218:2024, published by NSAI and effective from 01 October 2024, specifies minimum sound pressure levels that fire alarm sounders must achieve in different building types. These requirements are set out in Section 6.6.2 of the standard.

75 dB(A)

Bedrooms

Minimum in residential (institutional) buildings including nursing homes and hospitals

65 dB(A)

Common Areas

Or 5 dB(A) above ambient noise, whichever is greater

118 dB(A)

Maximum Limit

Shall not exceed at any point where people are likely to be present

I.S. 3218:2024, Section 6.6.2, Note 1: “Residential (institutional) means a hospital, nursing home, home for old people or for children, school or other similar establishment used as living accommodation or for the treatment, care or maintenance of persons suffering from illness or mental or physical disability, where such persons sleep on the premises.”

The 75 dB(A) requirement is intended to wake sleeping occupants in residential buildings. This is a widely accepted benchmark in fire safety for buildings where occupants can self-evacuate upon hearing the alarm. However, healthcare facilities present fundamentally different operational challenges where this assumption does not hold true.

Sound levels must be measured using an instrument conforming to I.S. EN 61672-1:2013, Class 2 or better, with slow (1 second) response and ‘A’ weighting. Fire alarm sounder frequencies shall be in the range of 500 Hz to 1,000 Hz.

The Risks of High Sound Levels in Healthcare Settings

While the goal of I.S. 3218:2024 is to enhance fire safety, its application in healthcare environments introduces several significant risks that may paradoxically impair the very safety outcomes the standard seeks to achieve.

Stress and Anxiety Among Residents

In nursing homes and hospitals, many residents suffer from dementia, Alzheimer’s, or other cognitive impairments. The sudden sound of a fire alarm at 75 dB(A) can induce confusion, panic, and agitation.

Research indicates that people living with dementia may no longer understand the sound of an alarm or what to do when they hear one. This may result in residents attempting to flee unpredictably, freezing in place, or reacting in ways that complicate evacuation efforts.

Health Risks for Vulnerable Populations

Sudden loud alarms can have physical health implications, particularly for individuals with pre-existing heart conditions, anxiety disorders, or stress-related health issues.

Sudden nocturnal awakening by loud alarms can trigger elevated heart rates, panic attacks, or cardiac events in already vulnerable individuals. There are documented risks to physical and psychological health due to the stress involved in alarm activations.

Impaired Staff Communication

In environments where occupants rely on staff to assist in evacuation, high sound levels can hinder rather than help the process. The alarm may drown out critical verbal instructions from staff.

This is not theoretical: The Quakers Hill nursing home fire demonstrated this exact problem in practice, with Fire and Rescue NSW documenting that the alarm system made communications difficult during evacuation.

Sensory-Sensitive Individuals

Many residents in healthcare settings, including those with autism or other sensory sensitivities, may experience heightened distress in response to loud sounds.

Sound levels of 75 dB(A) can cause extreme discomfort, leading to behavioural responses that complicate evacuation and increase risk of injury during an emergency.

Research Evidence: Dementia and Fire Alarm Response

A 2024 narrative review published in Frontiers in Rehabilitation Sciences found that for people with dementia during evacuation, it is recommended to give them “calm and proper instructions, lots of reassurance and close supervision.” The study noted that cognitive problems as well as dementia can significantly affect evacuation, with staff needing specific training on how to “help mitigate psychological distress and anxiety.”

Further research in PMC documented that “people living with dementia may no longer understand the sound of an alarm or what to do when they hear one,” highlighting the fundamental incompatibility between high-volume alarm systems and the needs of this population.

Sources: Frontiers in Rehabilitation Sciences (2024); PMC Narrative Review on Fire Risk and Dementia (2024)

Case Study: Quakers Hill Nursing Home Fire

Sydney, Australia | 18 November 2011

On 18 November 2011, a fire at Quakers Hill Nursing Home in Sydney resulted in 11 fatalities and the evacuation of approximately 88 aged, frail residents. Many suffered from dementia and some were bedridden. This tragic incident provides critical lessons about fire alarm systems in healthcare settings.

Key Finding: Alarm Communication Barriers

Fire and Rescue NSW’s post-incident analysis explicitly documented the challenges created by the alarm system:

“The alarm and building occupant warning system made communications difficult during the evacuation.”
Fire and Rescue NSW Recommendation:
“Staff must give clear concise instructions to residents during the evacuation, including visual gestures when background alarms make verbal communications impossible.”

This real-world incident demonstrates that high-volume alarm systems can actively impede evacuation effectiveness when staff cannot communicate with residents or coordinate their response. The coronial inquest also identified that there were numerous difficulties with the evacuations, including beds unable to fit through exit ramps, congestion at exit doors, and fire/smoke doors being opened during rescue allowing smoke to enter corridors.

Read the full Fire and Rescue NSW Lessons Learned report

Alternative Approaches: NHS Healthcare Guidance

The UK’s NHS healthcare fire safety guidance takes a fundamentally different approach to sounder levels in healthcare settings. This guidance recognises that the primary function of alarms in dependent-occupant environments is to alert staff, not to prompt self-evacuation by patients.

Sound Level Comparison: I.S. 3218:2024 vs NHS Guidance

Environment I.S. 3218:2024 NHS SHTM 82 Difference
Dependent patient areas 75 dB(A) 45-55 dB(A) 20-30 dB(A) lower
Self-evacuating areas 65 dB(A) or 5 dB above ambient Per BS 5839-1 Comparable
Mental health units 75 dB(A) (bedrooms) Reduced volume devices SHTM allows adaptation
NHS Scotland SHTM 82 (Fire Alarm and Detection Systems): “The audibility of the general alarm in areas where patients require assistance to evacuate need only be typically in the range 45-55 dB(A), or 5 dB(A) above the notional noise level, whichever is greater. As far as possible, sound pressure levels in excess of this should be avoided.”

Why the Different Approach?

The NHS guidance recognises fundamental differences in healthcare evacuation:

  • Function: In dependent-occupant environments, the alarm’s function is to alert staff, not to prompt self-evacuation by patients
  • Disturbance: High sound levels may cause confusion and distress to dependent patients, impeding rather than aiding evacuation
  • Communication: Staff need to communicate effectively during evacuation procedures
  • Visual alternatives: Visual alarm devices may be provided in areas where audible alarms are unacceptable (operating theatres, ITU, special care baby units)

The European Confederation of Fire Protection Associations has also recognised the value of silent evacuation systems in care homes, where staff are alerted via pre-alarm notification (warning lights or messaging systems) and have time to assess whether a fire exists before the general alarm sounds. This approach minimises distress to residents while maintaining fire safety.

Mitigating the Risks: A Balanced Approach

While the 75 dB(A) requirement in bedrooms is a safety-driven mandate, it may not be suitable for all healthcare environments. To mitigate potential risks while remaining compliant, several strategies can be employed:

Risk-Based Assessment

Healthcare facilities should assess the specific needs of their occupants and document a fire risk assessment that considers these needs. Where the standard’s requirements may introduce risks, management can seek documented variations.

This approach is consistent with fire safety engineering principles that allow alternative solutions where they can be demonstrated to provide equivalent safety.

Visual Alarms and Staff Notification

In areas where high sound levels might cause distress, install visual alarm systems (flashing lights conforming to I.S. EN 54-23) to complement or partially substitute audible alarms.

Staff notification systems can alert key personnel before the general alarm sounds, allowing time to prepare residents and coordinate evacuation.

Lower Sound Levels with Documented Variation

Following NHS guidance, consider implementing lower sound levels (45-55 dB(A)) in dependent-occupant areas as a documented variation.

This should be justified through the risk assessment process to demonstrate compliance with safety needs while addressing individual care requirements.

Multi-Sensor Detectors

Installing multi-sensor fire detectors can reduce false alarms, decreasing the likelihood of frequent, loud alarm activations that distress residents.

These detectors use multiple sensors (heat and smoke) to verify fire presence before triggering, ensuring alarms activate only when necessary.

Zoning and Two-Stage Alarms

Zoning the alarm system can limit impact by activating sounders only in affected areas. Pre-alarm systems notify staff before triggering building-wide alarms.

I.S. 3218:2024 permits two-stage alarm arrangements where the zone of alarm origin receives an “evacuate” signal while adjacent areas receive an “alert” signal.

Staff Training on Visual Communication

As highlighted by the Quakers Hill fire, staff must be trained to use visual gestures when background alarms make verbal communications impossible.

Regular evacuation drills should practise communication methods that work effectively despite alarm noise, including hand signals and visual cues.

Documentation Requirements

Any variation from the standard requirements must be:

  • Documented in the fire risk assessment
  • Justified by the specific characteristics of the occupant population
  • Compensated by alternative measures (visual alarms, enhanced staff training, staff notification systems)
  • Agreed with relevant stakeholders including fire authorities where appropriate

The goal is not to circumvent safety requirements but to achieve the same safety outcomes through measures better suited to the specific healthcare environment.

Key Takeaways

  • I.S. 3218:2024 requires 75 dB(A) in bedrooms of residential (institutional) buildings including nursing homes and hospitals
  • High sound levels can impair evacuation by preventing staff communication and causing resident distress, as documented at Quakers Hill
  • Fire and Rescue NSW found that “the alarm and building occupant warning system made communications difficult during the evacuation”
  • NHS guidance recommends 45-55 dB(A) for dependent-occupant healthcare areas, recognising the fundamentally different evacuation model
  • Risk-based variations are possible when properly documented and compensated with alternative measures
  • Staff notification systems, visual alarms, and zoning can help balance safety compliance with resident welfare
  • Staff training must include visual communication methods for when alarms make verbal instructions impossible

Conclusion: Safety in Context

The primary purpose of I.S. 3218:2024 is to enhance safety by ensuring fire alarms are audible enough to alert occupants in time for safe evacuation. However, this goal cannot be achieved in isolation, especially in healthcare environments where residents may be immobile, cognitively impaired, or sound-sensitive.

The standard’s requirement of 75 dB(A) in bedrooms is crucial for waking occupants in buildings where self-evacuation is expected. But in healthcare facilities, rigid adherence without flexibility can introduce new risks. The Quakers Hill fire demonstrates that alarm systems designed for life safety can paradoxically impede evacuation when they prevent effective staff communication.

To fully achieve the intended safety goals, it is essential that the standard is applied with adequate consideration for the specific environment. In healthcare settings, the welfare of residents must be prioritised alongside technical compliance. Fire safety must be balanced with the need to avoid causing distress, confusion, or harm to residents.

Standards like I.S. 3218:2024 exist to enhance safety, but they must be applied with context-sensitive adaptations in healthcare settings to ensure that they protect rather than harm.

Phoenix STS: Healthcare Fire Safety Expertise

Phoenix STS provides specialist fire safety consultancy and training for Irish nursing homes and healthcare facilities. Our services include fire risk assessments that consider the unique challenges of healthcare environments, including alarm system design and evacuation planning for dependent occupants.

Need Guidance on Healthcare Fire Alarm Compliance?

Phoenix STS can help you navigate the balance between I.S. 3218:2024 compliance and the welfare needs of your residents. Our fire risk assessments consider the unique characteristics of healthcare environments.

Disclaimer

This article is provided for general informational and educational purposes only. While every effort has been made to ensure accuracy by referencing official standards (I.S. 3218:2024) and authoritative guidance (NHS HTM 05-03, SHTM 82), this content does not constitute professional, legal, or regulatory advice. Fire alarm system design and installation should always be carried out by competent persons in accordance with applicable standards and in consultation with relevant authorities. Any variation from standard requirements should be documented, justified through risk assessment, and agreed with appropriate stakeholders. Phoenix STS accepts no liability for actions taken or not taken based on this article. Always consult the full text of I.S. 3218:2024 and seek professional fire safety advice for your specific circumstances.

About the Author

Patrick McDonnell (BEng Fire Engineering, F.IIRSM, M.IFSM, CMIOSH, MIHEEM, M.NFPA) is CEO of Phoenix STS and a Certified Member of the Institution of Occupational Safety and Health (IOSH). With extensive expertise in fire engineering and healthcare fire safety compliance, Paddy specialises in helping Irish nursing homes and designated centres meet HIQA Regulation 28 requirements.

As a Fellow of the International Institute of Risk and Safety Management and Member of the National Fire Protection Association, Paddy delivers CPD-accredited training programmes and conducts fire risk assessments to PAS 79:2020 standard across Ireland. His work focuses on practical, evidence-based solutions for healthcare facilities, particularly in nursing home fire safety management and emergency evacuation planning.

Paddy is registered with the National Fire Risk Assessors Register (NFRAR) and contributes to advancing fire safety standards through professional development initiatives and industry collaboration.

Connect with Paddy on LinkedIn